

Fire System PressurizationJockey Pump
Everything about jockey pumps: role in fire protection systems, sizing (1% of main pump flow per NFPA 20), setpoints and applicable standards.
What is a jockey pump?
A jockey pump (or pressurizing pump) is the fire-fighting system component that maintains the network's static pressure between two narrow setpoints, compensating for small leaks in joints, valves and sprinklers. It operates automatically and prevents the main pump from being triggered by pressure drops. Reference standards: NFPA 20 and ABNT NBR 16704.
How to size a jockey pump?
NFPA 20 (section A.4.26) recommends sizing the jockey pump at approximately 1% of the main pump flow. Example: a 500 GPM (113 m³/h) main pump requires a ~5 GPM (1.1 m³/h) jockey. The jockey pressure should be 5 to 10 psi above the main pump shutoff pressure.
Difference between jockey and main fire pump?
The main pump provides flow and pressure for fire-fighting (hundreds of m³/h). The jockey is much smaller (1% of main flow) and maintains static pressure when there is no fire. The jockey operates frequently in short cycles of a few minutes. The main pump only operates in real emergencies, when there is significant water demand.
Why can't the jockey pump be eliminated?
Without a jockey, any microscopic leak in the network (normal in systems with hundreds of joints) would cause pressure drops and repetitive main pump activation. This premature wear compromises the main pump's lifespan — when a real fire occurs, it may fail. That is why NFPA 20 and NBR 16704 require a jockey in every fixed fire-fighting system.
How to Size
Technical criteria for correct specification
Flow Rate
Approximately 1% of main pump flow (NFPA 20 A.4.26). Example: 500 GPM main pump = ~5 GPM jockey. Must be sufficient to compensate normal network leaks.
Pressure
Jockey shutoff pressure must be 5-10 psi (0.35-0.7 bar) above main pump shutoff pressure. This ensures the jockey maintains network pressure without interfering with main pump start logic.
Construction
Vertical multi-stage centrifugal in stainless steel AISI 304 or 316. Vertical configuration saves space on the skid. Multiple stages provide high pressure at low flow — exactly the jockey profile.
Motor
Electric, typically 1-5 hp. Direct start for motors up to 7.5 hp or soft-starter for higher powers. Three-phase 220/380/440V per installation. Thermal protection mandatory.
What Is a Jockey Pump?
Function, sizing and importance in fire systems

The jockey pump (or pressure maintenance pump) is a fire protection system component whose function is to maintain the static pressure of the network between two narrow setpoints, compensating for small leaks in joints, valves and sprinklers. It operates automatically and prevents the main pump from unnecessary starts.
Sized at approximately 1% of the main pump flow (NFPA 20 A.4.26), the jockey is typically a vertical multi-stage centrifugal pump in stainless steel 304 or 316. FB Bombas supplies jockey pumps as an integrated part of fire fighting skids, with control panel, valves and instrumentation pre-configured.
Flow: ~1% of main pump (NFPA 20 A.4.26)
Pressure: 5-10 psi above main pump shutoff
Construction: vertical multi-stage, SS 304/316
Operation: automatic via pressure setpoints
How Does a Jockey Pump Work?
Automatic pressure maintenance cycle
Leak Detection
Small leaks in joints, valves and sprinklers cause gradual pressure drop in the network. The pressure switch continuously monitors and detects when pressure reaches the lower setpoint (jockey start point).
Auto-Start
Upon reaching the lower setpoint, the control panel starts the jockey pump automatically. It restores network pressure with small flow (~1% of main), compensating the leak without activating the fire pump.
Auto-Stop
When pressure reaches the upper setpoint (typically 5-10 psi above main pump shutoff), the jockey stops. If pressure keeps dropping after jockey starts, it indicates real demand — the panel activates the main pump.
Jockey vs. Main Pump
Fundamental differences between the two devices
| Criteria | Jockey | Main Pump |
|---|---|---|
| Function | Maintain static pressure | Fire fighting |
| Flow rate | ~1% of main (1-5 GPM) | 100% (500-2500 GPM) |
| Pressure | 5-10 psi above main | System rated pressure |
| Operating frequency | Short daily cycles | Emergency only |
| Motor | 1-5 hp electric | 25-500 hp electric or diesel |
| Cost | 5-10% of total system | Main component |
Standards & Regulations
NFPA 20, NBR 16704 and installation requirements
Standard for the Installation of Stationary Pumps for Fire Protection. Defines requirements for jockey, main and standby pumps. Section A.4.26 specifies jockey sizing at ~1% of main pump flow.
Brazilian standard for stationary fire protection pump installation. Aligned with NFPA 20, requires automatic pressure maintenance pump with setpoint logic and independent control panel.
Setpoint Logic
Lower setpoint (jockey start) > main pump start setpoint > standby start setpoint. Upper setpoint (jockey stop) must be 5-10 psi above main pump shutoff. Prevents conflict between pumps.
Control Panel
Dedicated or integrated panel. Must have run/fault indication, manual/auto mode and motor thermal protection. Independent power supply from normal grid (generator or dedicated circuit).
Frequently Asked Questions
What is a jockey pump?
The jockey pump (or pressure maintenance pump) is a fire protection system component whose function is to maintain the static pressure of the network between two narrow setpoints, compensating for small leaks in joints, valves and sprinklers. It operates automatically and prevents the main pump from unnecessary starts.
How to size a jockey pump?
NFPA 20 (section A.4.26) recommends sizing the jockey pump at approximately 1% of the main pump flow. Example: if the main pump is 500 GPM (113 m3/h), the jockey should be ~5 GPM (1.1 m3/h). Jockey pressure must be sufficient to reach the system upper setpoint — typically 5-10 psi above main pump shutoff pressure.
What is the difference between jockey pump and main fire pump?
The main pump provides the flow and pressure needed for fire fighting (hundreds of m3/h). The jockey pump is much smaller (1% of main flow) and only maintains static pressure when there is no fire. The jockey operates frequently in short cycles; the main pump operates only in real emergencies.
What standards regulate jockey pumps?
The main standards are NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection) and NBR 16704 (Stationary pump installation for fire protection). Both require automatic pressure maintenance pump with setpoint logic and independent control panel.
Why can't the jockey pump be eliminated from the project?
Without the jockey, any microscopic leak in the network (normal in systems with hundreds of joints) would cause pressure drops and repetitive main pump starts, wearing it prematurely. When a real fire occurs, the main pump may have compromised service life.
Can a jockey pump be centrifugal?
Yes. The jockey pump is typically a vertical multi-stage centrifugal pump in stainless steel (304 or 316), sized for low flow and high pressure. FB Bombas supplies jockey pumps as an integrated part of fire fighting skids, with control panel, valves and instrumentation pre-configured.
What does continuous jockey pump operation mean?
If the jockey pump operates continuously without stopping, it signals a significant system leak — larger than the jockey's replenishment capacity. Investigate immediately: check open sprinklers, leaking valves, damaged joints. Normal jockey operates in short cycles of a few minutes.
How much does a fire jockey pump cost?
Jockey pump cost varies by flow, pressure, material and panel configuration. FB Bombas supplies the complete system (jockey + main + diesel + panel) as an integrated skid. Request a quote with your project data for specific pricing.
Companies that Trust FB Bombas
80+ years supplying fire protection systems to industry
Need a jockey pump?
Send us your fire protection project data. Our engineering team sizes the jockey pump and complete system for your application.
Onde esta linha é especificada
Setores e cenários cobertos com cluster pages técnicos da FB Bombas.
Related content
Technical articles, essential definitions and products curated by FB Bombas engineering.
Technical Articles
- Fire-Fighting Systems: NFPA 20 & NBR 16704
- Cavitation: How to Identify and Prevent
- NPSH: Practical Calculation
Products & Resources
Compare before you specify
Accelerated technical decision — side-by-side guides with real criteria and data from official manuals.
- COMPARISON
Brazilian vs Imported Pump: TCO and Lead Time
When the math moves from purchase price to TCO — spare parts, lead time, FX risk and technical support — the balance shifts. These are the variables an industrial buyer should weigh.
See comparison - COMPARISON
Which FB pump to use — decision by fluid and condition
Four families, four decisions. Start with fluid, cross through temperature and end on flow. Each answer links directly to the matching series.
See comparison


