Skip to main content

NFPA 20 and NBR 16704 Fire Pump: Systems, Applications and Selection

FB Bombas central guide to fire pumps: what each standard covers, how to organize flow, pressure and NPSH, what changes between electric and diesel drives, and which documents to request for the set. The occupancy and component guides go deeper into each decision.

Fire pumps on pallets in a workshop, from the FB Bombas collection
FBFS series — photograph from the FB Bombas collection.

FB Bombas technical answer

A fire pump delivers the flow and pressure that the hydraulic calculation requires at hydrants, hose reels and automatic sprinklers. NFPA 20 covers the installation of stationary fire protection pumps, NBR 16704 sets the requirements for stationary pump sets serving automatic systems, and NBR 10897 and NBR 13714 cover the systems the pump supplies. Selection starts from the design demand, the suction condition and the available power; the set is electric, diesel or combined, with a jockey pump when the network must stay pressurized. This page organizes standards, sizing, documents and the guides by occupancy and component.

FB pump for this application

1. Fire pump standards: NFPA 20, NBR 16704 and NBR 13714

NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection) is the NFPA standard for installing stationary fire protection pumps. It covers centrifugal, vertical turbine and positive displacement pumps, electric and diesel drives with their controllers, the power supply, the fuel tank and acceptance testing. NBR 16704 sets the requirements for stationary pump sets serving automatic fire protection systems.

NBR 13714 (hydrant and hose reel systems) covers the system the pump supplies and therefore the demand. The ABNT Catalog record lists it as in force, confirmed on 25 April 2024. What sets the system type, flow, pressure and fire water reserve required on the job is the state Fire Department Technical Instruction, in Tables 2 and 3 of São Paulo's IT 22 and Goiás' NT 22; the NBR 13714 article gives the values with the state of each one.

Each Brazilian state publishes the regulations its Fire Department applies to design review and inspection. In São Paulo, CBPMESP Technical Instruction IT 22 covers hydrants and hose reels and gathers the fire pump rules in Annex C; IT 23 covers automatic sprinklers. In Goiás, CBMGO NT 23 requires sprinkler pump sets to follow Annex C of NT 22 and NBR 16704, and requires those pumps to operate under positive pressure, with no priming tank.

These rules apply in the jurisdiction that published them.

Note

A design standard, a product certification and an installation approval are different things. NFPA and ABNT publish standards; the listing or certification of a model is proven only by the document issued by the body that granted it; in São Paulo, the AVCB is issued by the Fire Department for the building (State Decree 69.118/2024, art. 3, XI). Request the evidence for each one by document name.

1.1 NBR 16704: installation of the pump set

According to the ABNT Catalog record, NBR 16704 sets the minimum requirements for the selection and installation of stationary pump sets for automatic fire protection systems, and is in force. It is the Brazilian reference for installing the set, alongside NFPA 20. In Goiás, NT 23 requires sprinkler pump sets to follow Annex C of NT 22 and NBR 16704.

The record states that the standard has a certification program. The certification of a model is proven only by the certificate issued for it; FB declares the pump set design in conformity with NFPA 20.

2. Technical guides by occupancy type

Occupancy changes the input data, not the selection method. The local rule classifies the building by built area and occupancy and thereby sets the system type and the minimum reserve; in São Paulo, that classification is in Table 3 of IT 22. The pump comes from the hydraulic calculation in the design report, with the two most unfavourable jets in simultaneous use, and IT 22 does not accept a reference to another project to justify the sizing.

The guides below detail the decisions for each type of building. Use them with the current revision of the design report to prepare the technical enquiry.

  • Warehouses and distribution centres: protection depends on the goods and the storage arrangement; in Goiás, NT 23 requires any storage, even temporary, to be protected under NBR 16981.
  • Shopping centres, hospitals and residential buildings: occupied buildings with hydrants and, depending on classification, automatic sprinklers; IT 22 in São Paulo (C.1.2) and NT 22 in Goiás (C.1.1) require a pump room with access all around the pumps and space to remove any of them.
  • Power plants, refineries and terminals: in São Paulo, protection of tanks and tank farms follows IT 25; when those tanks are separated from other buildings under IT 25, the hydrant reserve is not added to the reserve of the cooling and foam systems (IT 22, 4.12.2 and 4.12.6).
  • Preassembled skid: the set is mounted on a metal baseplate according to the contracted arrangement; the suction, discharge, power and exhaust interfaces are defined in the design, and the components and scope of supply in the proposal.

3. Technical guides by system component

The set comprises the main pump, the pressure maintenance (jockey) pump, the driver, the control panel and the valves.

Goiás' NT 22 defines the fixed pump as the one meant to deliver water to the fire-fighting systems (item 4.4), the booster pump as the one that supplies the hydraulically most unfavourable hydrants or hose reels when the elevated reservoir alone cannot supply them (item 4.3) and the jockey pump as the centrifugal hydraulic device that keeps the system pressurized within a preset range (item 4.5).

In São Paulo, Annex C of IT 22 sets rules that apply to any driver. The fire pump serves that purpose only and is protected against mechanical damage, weather, chemicals, fire and moisture. The main pump is directly coupled through a flexible coupling, without belts or chains, with an isolating valve upstream and a check valve plus an isolating valve downstream.

After an automatic start, shutdown is manual only, at the panel in the pump room, and the pump must reach full operating speed in about 30 s.

  • Electric motor: power supply independent of the general load, a switch marked “ALIMENTAÇÃO DA BOMBA DE INCÊNDIO – NÃO DESLIGUE” (fire pump supply – do not switch off), magnetic starting and acceleration within 10 s (IT 22, C.2.7, C.2.11 and C.2.18).
  • Diesel engine: full-load operation for 6 uninterrupted hours, a speed governor holding rated speed within 10%, two battery sets with a dual charger, and recharge of a discharged battery within 24 h (IT 22, C.3.1.4, C.3.2, C.3.10 and C.3.11).
  • Jockey pump: required in São Paulo when the network has more than six outlets, except with an elevated reservoir; maximum flow of 20 L/min and maximum pressure equal to the main pump shutoff, with about 100 kPa (10 m of water) recommended between sequential starts (IT 22, C.1.15 and C.1.15.1).
  • Sprinklers and hydrants: each system’s demand comes from its own standard, and IT 22 allows reserves to be interconnected under the parameters of IT 23.

4. Decision flow: which guide to use at each project stage

The starting guide depends on the project stage. At concept stage, begin with the occupancy guide, which organizes classification, required systems and input data. At specification stage, move on to the component guides and the sizing article. During construction and acceptance, use the pump room, commissioning and maintenance guides.

Which guide to consult at each project stage
Project stageRecommended guide
Concept and design report: classification, required systems and reserveOccupancy guide: warehouse, shopping centre and hospital, power plant and refinery
Pump specification: flow, pressure, suction and curveArticle: How to size an NFPA 20 fire pump
Driver selection: available power, starting and fuelElectric motor and diesel engine guides
Network pressurization: pressure range and starting sequenceJockey pump guide
Supply definition: scope, interfaces and acceptancePreassembled skid guide
Combined systems: hydrants and sprinklersSprinkler and hydrant guide
Installation and operation: pump room, testing and maintenancePump room and NFPA 25 articles

5. Sizing: flow, pressure, NPSH and curve

Design flow is the largest simultaneous demand in the design report. In São Paulo, hydrant and hose reel systems range from type 1 to type 5 in Table 2 of IT 22, with a minimum flow of 100 to 600 L/min at the valve of the most unfavourable hydrant, and the calculation considers the two most unfavourable jets in simultaneous use.

For automatic sprinklers, the hazard classification and the design area come from the system’s technical standards; in Goiás, NT 23 accepts NFPA 13 where Brazilian standards are silent.

Total head is the sum of the elevation difference, the friction losses and the pressure required at the most unfavourable point. IT 22 accepts Darcy-Weisbach or Hazen-Williams and gives the new-pipe C factor by material: 100 for unlined cast or ductile iron and for black steel in dry systems, 120 for black steel in wet systems and for galvanized steel, 140 for cement-lined cast or ductile iron and 150 for copper and plastic.

Working pressure at the nozzles may not exceed 100 m of water (1,000 kPa), and IT 22 does not recommend fire pumps above 100 m of water (1 MPa).

On the suction side, IT 22 limits velocity to 2 m/s under suction lift and 3 m/s under positive suction, and to 5 m/s in the rest of the piping (items 4.8.11 and 4.8.12 of São Paulo's IT; items 5.8.9 and 5.8.10 of Goiás' NT). Under suction lift, available NPSH is calculated at 1.5 times the system rated flow and must be equal to or greater than the NPSH required from the pump curve at that flow.

IT 22 prefers positive suction and only accepts pumps with suction above the water level in type 1, 2 and 3 systems, with a dedicated suction pipe, a foot valve with strainer and a priming tank.

The curve must cover the design report demand within the range the adopted design standard allows for the pump. The readings of the field acceptance test come from the testing chapter of the adopted standard (Chapter 14 in NFPA 20): ask for the procedure and the test points in the proposal.

In São Paulo, IT 22 requires pumps rated above 600 L/min to have a continuous water flow through a 6 mm tube or orifice plate taken from the volute, to prevent overheating.

Key point

The article “How to size an NFPA 20 fire pump” shows the full calculation, from the rated point to the 150% point, with numerical examples of flow, total head, NPSH, diesel tank and jockey settings.

6. Industrial main fire pump: what to verify in the proposal

A catalogue centrifugal pump may have the same rated point as the design and still not qualify as a fire pump. What decides is the curve from shutoff to 150% of flow, the coupling, the driver, the control panel and the set’s documentation. The table sets out what the rule requires and the evidence the proposal must include.

What the rule requires and the evidence to request in the proposal
AspectWhat the rule requiresEvidence in the proposal
CurveThe curve covers the design report demand within the range of the adopted design standard (NFPA 20 or NBR 16704)Curve for the offered model, impeller and speed
TestingNFPA 20: field acceptance test under Chapter 14, with the readings set by the procedureField acceptance procedure and record of readings
CouplingIT 22 (SP): direct, flexible coupling, no belts or chainsSet drawing showing base and coupling
Pump nameplateIT 22 (SP): manufacturer, serial number, model, rated flow and pressure, speed and impeller diameterNameplate data in the datasheet
Electric motorIT 22 (SP): magnetic starting and acceleration within 10 sWiring diagram and panel bill of materials
Diesel engineNFPA 20 (current edition, 11.4.1.3.1): 12 h of engine run time at the published consumption, plus 5% for expansion and 5% for sump; IT 22 (SP): twice the water reserve durationTank calculation and battery specification
SuctionIT 22 (SP): available NPSH at 1.5 times rated flow, under suction liftAvailable NPSH calculation and NPSH required curve

Warning

A standard quoted in the proposal is not evidence. Request the curve, datasheet, drawings and reports that identify the equipment actually offered.

7. Documentation for the Fire Department inspection (AVCB)

In São Paulo, the AVCB is issued by the Fire Department for the building (State Decree 69.118/2024, art. 3, XI). It belongs to the building, not to the pump: the supplier delivers the set’s documents, and the design and installation complete the process. IT 22 requires a design report with calculations, sizing and an isometric view of the piping, and does not accept a reference to another project to justify any information.

After the inspection, the São Paulo regulation assigns maintenance and periodic testing of the safety measures to the owner or the party responsible for use, in accordance with the specific technical standards (State Decree 69.118/2024, art. 15, II). The list below gathers the set documents that feed the process.

  • Datasheet and Q×H curve for the offered model, impeller and speed.
  • Pump nameplate with manufacturer, serial number, model, rated flow and pressure, speed and impeller diameter (IT 22, C.2.15).
  • Electric motor nameplate with manufacturer, type, model, serial number, power in CV, speed, voltage, current and frequency (C.2.16), or diesel engine nameplate with continuous-duty power and rated speed (C.3.8).
  • Control panel with dimensional drawings, layout, wiring diagram, terminal strip, internal diagram and bill of materials (C.2.18.4).
  • Dimensional drawing of the set and of the site interfaces.
  • Installation, operation and maintenance manuals for the equipment.
  • System commissioning report; IT 22 provides a template in Annex F.

8. Planning stages: from order to acceptance

Timing depends on approvals, components and site readiness, and is confirmed in the proposal. For field acceptance, the pump test follows the adopted standard's procedure, with the readings recorded point by point.

Stages, conditions and records; timing and responsibilities are defined in the contract.
StageCondition to proceedExpected record
Assessment and proposalDesign report, reserve levels and available powerSelection, scope and document list
Drawing approvalInterfaces coordinated with the pump roomApproved drawing revision
Manufacturing and assemblyComponents and requirements definedNameplates and component list
Shipping and receiptLifting and destination plannedReceiving inspection
Installation and commissioningSuction flushed, power and fuel availableField test under the adopted standard's acceptance procedure
Operational handoverAcceptance and responsibilities definedCommissioning report and maintenance plan

9. Mistakes to avoid in fire pump projects

Each item below has an objective check in the design report, the proposal or the installation. Record the answer in the supply documentation. References to IT 22 apply to São Paulo.

  • Selecting on the rated point alone, without checking the demand up to 150% of flow and the shutoff against the adopted standard’s envelope.
  • Calculating available NPSH at rated flow: under suction lift, IT 22 requires 1.5 times the system rated flow.
  • Designing suction above the water level in a type 4 or 5 system: IT 22 only accepts that condition in types 1, 2 and 3.
  • Using belts or chains between driver and main pump, where IT 22 requires direct flexible coupling.
  • Connecting the electric pump downstream of the building main switch, so that a general shutdown also cuts the pump; IT 22 requires a supply independent of the general load.
  • Programming automatic shutdown of the main pump: after starting, shutdown must be manual, at the panel in the pump room.
  • Sizing the diesel tank without the selected engine’s consumption or without the applicable rule (NFPA 20 or IT 22).
  • Setting the jockey pump above the main pump shutoff or without a differential between starts; IT 22 recommends about 100 kPa (10 m of water) between sequential starts.
  • A pump room without access all around the pumps, without space to remove any of them, or housing machinery other than water-based fire protection or domestic water pumps.
  • Applying another state’s rule or copying another project: IT 22 does not accept references to another project in the design report.

Note

For a focused enquiry, send the current revision of the design report, the reserve levels, the available power and the list of required documents.

Quote a fire pump system designed to NFPA 20

Share the flow, pressure, proposed drivers and standards required by the fire-protection design. The quotation should identify the configuration, curve and documents included in the supply.

Request NFPA 20 system quote

Frequently asked questions

Technical answers about selection, installation and operation in this application.

What is the NFPA 20 standard?

NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection) is the NFPA standard for installing stationary fire protection pumps. It covers centrifugal, vertical turbine and positive displacement pumps, electric and diesel drives with their controllers and acceptance testing. FB's supply is a design in conformity with NFPA 20, backed by the set’s curve and documents.

Which standard governs fire pumps in Brazil?

There is no single standard. NBR 16704 sets the requirements for stationary pump sets serving automatic fire protection systems, and NFPA 20 applies when the design or the purchaser adopts it. NBR 10897 (automatic sprinklers) and NBR 13714 (hydrants and hose reels) cover the systems served. On top of that, the state Fire Department regulations apply: in São Paulo, IT 22 gathers the fire pump rules in Annex C; in Goiás, NT 23 refers sprinkler pumps to Annex C of NT 22 and to NBR 16704.

Which industrial fire pump should be used?

The right industrial fire pump is the one that meets the design demand with its curve inside the adopted standard’s envelope and with suction suited to the installation. With positive suction, end-suction, in-line or split-case centrifugal pumps are used; where a static suction lift is required, NFPA 20 does not allow those pumps and the case calls for a vertical turbine pump. The electric, diesel or combined drive follows from the available power and the applicable rule. FB Bombas builds the FBFS electric, diesel and electric + diesel configurations, with jockey pump and control panel.

Electric or diesel fire pump: which to choose?

Occupancy alone does not decide. Compare power reliability, source independence and the applicable rule. With an electric motor, in São Paulo, IT 22 requires a supply independent of the general load and allows a standby generator; NFPA 20 addresses the alternate source and the transfer at the controller. With diesel, NFPA 20 requires a tank for at least 12 hours of engine run time, based on the manufacturer’s published consumption, plus 5% for expansion and 5% for the sump (the ongoing NFPA 20 revision proposes 8 hours; check the edition adopted in the design); in São Paulo, IT 22 requires fuel for twice the operating time of the water reserve and two battery sets. When the design requires redundancy, the FBFS electric + diesel configuration combines both drives.

Can the jockey pump be eliminated to reduce cost?

The decision comes from the applicable rule, not from cost. In São Paulo, IT 22 requires a jockey pump when the hydrant or hose reel network has more than six outlets and waives it when the fire reservoir is elevated, whatever the number of outlets. The jockey pump's function is to keep the network pressurized within a preset range and compensate small pressure losses, with a maximum flow of 20 L/min (item C.1.15 of São Paulo's IT; item C.2.1 of Goiás' NT). Confirm the criterion and its exceptions with the designer before removing it from the specification.

When is a complete preassembled skid the right solution?

When the scope allows pumps, drivers, panel and accessories to be integrated on a single base and the pump room can house the set with access all around and space to remove any pump, as IT 22 in São Paulo (C.1.2) and NT 22 in Goiás (C.1.1) require. In the FB skid, the set is mounted on a metal baseplate according to the contracted arrangement; before comparing proposals, check the scope of supply, transport, lifting and the suction, discharge, power and exhaust interfaces.

What is the maintenance interval for a fire pump?

The interval comes from the standard adopted for inspection, testing and maintenance, such as NFPA 25, and from the equipment manuals. In São Paulo, the fire safety regulation assigns maintenance and periodic testing to the owner or the party responsible for use, in accordance with the specific technical standards (State Decree 69.118/2024, art. 15, II), and IT 22 provides in Annex F a template for the commissioning and periodic inspection report. Separate inspection, testing and maintenance by component and record results and responsibilities.

Does FB Bombas provide documentation for Fire Department approval?

FB Bombas delivers the set documentation defined in the contract, such as datasheet, Q×H curve and dimensional drawing. Approval rests with the Fire Department, based on the building’s design and installation. In São Paulo, IT 22 requires nameplates on the pump and drivers and, for the electric panel, dimensional drawings, layout, wiring diagram, terminal strip and bill of materials; include these items in the proposal’s document list.

Do I need a UL-listed or FM-approved pump, or is NBR 16704 enough?

It depends on what the design, the purchaser or the insurer requires. A listing or approval is product evidence, issued by a body for a specific model; NBR 16704 and NFPA 20 are requirement standards, and the certification of a model is proven only by the document issued for it. If the specification calls for a listing, request the document for the offered model, with scope and validity; if it calls for design compliance, request the set’s curve and datasheet.

What is the lead time for a complete fire pump system?

FB Bombas states the lead time in the proposal, once the set (pump, driver, panel and jockey pump) and the delivery location are defined. Send the design report and the list of required documents so that the proposal already accounts for those stages.

What warranty and after-sales support apply to fire pump systems?

Warranty and service terms are stated in the proposal and supply documents for each set. Confirm there the coverage for pump, driver and panel, the installation when contracted, and field services such as commissioning.

Does FB Bombas retrofit older fire pump systems?

Yes. Retrofit is part of FB Bombas special solutions. For an assessment, send the pump and driver nameplates, curves, drawings, test history and the current design demand. The analysis checks whether pump, driver and panel meet the adopted standard and the local rule, without assuming suitability from a pump replacement alone.

Next steps

Continue to product documentation, related applications or talk with our technical team.

To start the assessment

Share the fluid, flow, pressure and operating temperature. Include suction conditions and details of the installed equipment, if any. This context helps the FB Bombas team assess your application.

  • Fluid and operating conditions
  • Required flow and pressure
  • Installation and existing equipment

NFPA 20 and NBR 16704 Fire Pump: Systems, Applications and Selection