A pumped fire fighting system combines a water source, main pump, driver, controller and network. The jockey pump maintains network pressure, and the standby pump and alternate power depend on the standard and the design.
Read the complete answer
NFPA 20 covers pump installation; for hydrants, NBR 13714 and state technical instructions, such as those of São Paulo and Goiás, set items such as automatic starting and manual-only stopping. In an FB Bombas enquiry, identify the assembly and included services.
FB Bombas pump for this application

Do you need the pump for the fire-fighting system?
FBFS sets carry an FBCN main pump, a jockey pump, a control panel and a base, with electric, diesel or electric plus diesel drive, designed in accordance with NFPA 20 or ABNT NBR 16704, when specified.
Source: FBFS
At a glance
- Water supply, pumping, controls and network must match the design demand.
- Jockey pumps maintain pressure; flow and settings depend on network and adopted requirements.
- Electric, diesel and redundancy are design decisions, not universal occupancy packages.
- Assess FBCN using the configuration curve and suction and driver conditions.
- Define documents, interfaces and services in the agreed scope.
See which data to gather to select an assembly and check installation and maintenance scope.
1. System components and interfaces
Protection depends on compatibility between water supply, pumping, controls and distribution. Specifications should identify each component’s role and installation requirements. The pump assembly is one part of that architecture; delivery does not replace the building design.
In NFPA 20, the pump, driver and controller must comply as one unit, and a single entity is responsible for the performance of the pump, driver, controller and transfer switch.
For hydrant and hose systems, NBR 13714 and state technical instructions, such as São Paulo IT 22 and Goiás NT 22 (CBMGO), add requirements for the pump room, valves, automation and signalling. The components to specify are:
- Main pump — selected for hydraulic demand, suction and acceptance criteria; assess FBCN using the proposed configuration curve
- Driver — electric motor or diesel engine, chosen by available power and the applicable rule (section 2)
- Jockey pump — maintains pressure and makes up small losses; for hydrant and hose systems, São Paulo IT 22 and Goiás NT 22 limit its flow to 20 L/min and require it above six outlets, except with an elevated reservoir (São Paulo IT, C.1.15; Goiás NT, C.2.1)
- Controller — commands, signals, power supply and protection appropriate to the specified fire duty
- Valves — on the main pump, São Paulo IT 22 and Goiás NT 22 require an isolation valve upstream and, downstream, a check valve and another isolation valve (São Paulo IT, C.1.5; Goiás NT, C.1.6); other functions and supervision follow the arrangement
- Instrumentation — a pressure gauge on the main pump discharge and a compound gauge on the suction where it is negative (São Paulo IT and Goiás NT, C.1.17), plus the measurement and supervision required for operation and testing
- Pump room — access all around the pumps, space for maintenance and for removing any of them, and protection of the pumps against mechanical damage, weather, chemicals, fire and moisture (São Paulo IT, C.1.2 and C.1.4; Goiás NT, C.1.1 and C.1.5)
2. Electric drive, diesel drive and redundancy
In NFPA 20, an electric fire pump needs a normal power source that is continually available. Where that source is not reliable, or where the power serves a high-rise building, the standard requires an alternate source.
The requirement falls away if a backup pump driven by an engine, a steam turbine or an electric motor with an independent source is installed.
Local rules may go further. For hydrants, Goiás NT 22 (CBMGO) sets the minimum number of pumps by function: a booster pump is one main pump with a standby power source; a fixed pump uses a main and a standby pump, the latter with standby power, plus a jockey where needed.
Low-risk buildings, with a fire load of up to 300 MJ/m², need no standby pump, and the main pump then gets the standby power source.
Under the same rule, the main and standby pumps must not run at the same time: if the standby pump is running because of a power failure, the electric main pump must not start when power returns. The standby source can be a generator or another source, such as batteries, and may be waived with an internal combustion pump.
Goiás NT 22 (CBMGO) also sets the minimum autonomy of booster and fixed pumps running at full load: 2 hours for a fire load of up to 1,200 MJ/m², 4 hours from 1,200 to 2,400 MJ/m² and 6 hours above 2,400 MJ/m².
FB Bombas supplies the FBFS line in three configurations, which illustrate driver and redundancy alternatives. They are not standard packages and do not imply automatic approval for an occupancy. Selection must consider available power, demand and applicable regulations. The table summarises what to check in each.
| Configuration | Components | What to check |
|---|---|---|
| Electric | Electric main pump + jockey + control panel | Power supply, alternate power source and controller |
| Diesel | Diesel main pump + jockey + dedicated controller | Duty point, starting, fuel tank, ventilation, cooling and exhaust |
| Electric + Diesel (redundant) | Electric pump + diesel pump + jockey | Role of each pump, dedicated controls and sequence |
3. Applicable standards: NFPA 20 and NBR 16704
NFPA 20 covers the selection and installation of stationary pumps for fire protection, including supply, suction, discharge, power, drivers, controls and acceptance tests. It does not set the system’s flow and pressure demand or periodic inspection, testing and maintenance, which are the subject of NFPA 25. Applying it requires identifying the edition, assembly type and design criteria.
NBR 16704 covers stationary pump assembly requirements for automatic fire protection systems. NBR 10897 and NBR 13714 address sprinklers and hydrant and hose systems respectively. Check local rules and adopted editions; different references are not automatically equivalent.
For hydrant and hose systems, Annex C of São Paulo IT 22 and that of Goiás NT 22 set out the pump requirements:
- at least one electric or internal combustion pump, used only for fire protection;
- a main pump directly coupled through a flexible coupling, without belts or chains;
- automatic start by simply opening any hydrant;
- full speed in about 30 seconds (São Paulo IT, C.1.1, C.1.3, C.1.5, C.1.8 and C.1.9; Goiás NT, C.1.2, C.1.6, C.1.9 and C.1.10).
Both also allow, for example, manual starting at each hydrant or hose station in networks of up to six points (São Paulo IT, C.1.10; Goiás NT, C.1.11).
List standards, editions and required acceptance documents in the enquiry. Confirm which records and services accompany the supply.
4. How to size the system — required data
Occupancy, materials and process assessment determines the systems to design. The design calculations establish demands and simultaneity under applicable references. Select the pump from those results and actual supply conditions.
For a centrifugal fire pump, NFPA 20 requires the greatest single demand of any system connected to it to be no more than 150% of rated flow, with a rated net pressure of at least 40 psi (2.7 bar).
The curve also has limits: at 150% of flow, at least 65% of rated head, and a shutoff head of no more than 140% of rated. The data to gather are:
- Flow — hydraulic demand and simultaneity documented in the design
- Head — energy balance with elevation, losses, available and required residual pressure
- Driver — available energy, required backup and operating conditions
- Site — space, access, environment, water source, minimum level and suction losses; São Paulo IT 22 and Goiás NT 22 prefer positive suction and still treat it as such with the pump shaft up to 2 m above the reference water level, or at 1/3 of the reservoir’s effective capacity, whichever is less (São Paulo IT, C.1.12; Goiás NT, C.1.13)
- Maximum pressure — São Paulo IT 22 and Goiás NT 22 do not recommend fire pumps with pressures above 100 m of water column, or 1 MPa (São Paulo IT, C.1.14; Goiás NT, C.1.15)
5. Starting and control sequence
In a system with a jockey pump, the network is pressurised within a preset range and the pumps are at rest. A small pressure drop starts the jockey pump, and a larger drop, such as a hydrant opening, starts the main pump.
In São Paulo IT 22 and Goiás NT 22, pressure-switch automation starts and stops the jockey, only starts the main pump, and the recommended difference between sequential starts is about 100 kPa (10 m of water column) (São Paulo IT, C.1.15.1 and C.1.15.2; Goiás NT, C.2.2 and C.2.3).
Starting and stopping points and standby operation must be coordinated in the design. The sequence depends on the controller and regulations; do not set pressure switches by copying another installation’s pressure differences.
In hydrant and hose systems, an automated main pump starts by itself but does not stop by itself. In São Paulo IT 22 and Goiás NT 22 (CBMGO), once the motor starts, the main or booster pump (in NT 22, the fixed or booster pump) can only be stopped manually.
In IT 22, at its own control panel in the pump room (São Paulo IT, C.1.6; Goiás NT, C.1.7).
Both also require at least one manual start point in a safe, easily accessible place, and NT 22 allows that point to stop the pump as well. Record that stop logic in the design, confirm the controls that apply to your system and train those responsible for operation and tests (São Paulo IT, C.1.7; Goiás NT, C.1.8).
NFPA 20 also keeps pressure sensing separate: no controller, not even the jockey pump controller, shares a sensing line; each has its own, connected between its pump’s discharge check valve and discharge isolation valve.
The signalling panel for main or booster pumps has a push button to start them manually and visual and audible signals.
For an electric pump, it shows at least panel energised, pump running, phase failure and loss of power to the starting control; for an internal combustion pump, panel energised, pump running, low battery charge and selector switch in manual or panel off (São Paulo IT and Goiás NT, C.1.16).
Record settings during commissioning. If jockey cycling becomes abnormal, investigate losses, pressure, instruments and controls before changing setpoints.
6. The routine that keeps the system alive: testing per NFPA 25
NFPA 25 requires a weekly no-flow test on a diesel pump, for at least 30 minutes, and a monthly one on most electric pumps, for at least 10 minutes.
Four electric pump cases remain weekly unless a redundant fire pump is provided, in which case they may move to monthly; they include vertical turbine pumps and pumps serving buildings beyond the fire department’s pumping capacity.
Once a year, the flow test produces the field curve: zero flow (churn), 100% of rated flow and the maximum flow, up to 150% of rated. The no-flow test confirms the start; the annual test, the hydraulic performance.
In the weekly inspection of a diesel system, the standard checks, among other items, that the fuel tank is at least two-thirds full, the controller selector is in automatic and battery voltage and charging current are normal.
The standard’s annex gives as examples of impairment a pump that did not start automatically in the test, a suction or discharge valve not fully open and a diesel controller selector out of automatic.
Inspection, testing and maintenance plans need to identify the applicable standard edition, equipment and procedures. No-flow tests check different functions from flow performance tests. Frequency, duration and supervision must follow adopted references and manuals, not one rule for diesel and electric drivers.
Record initial conditions, measured parameters, anomalies and corrective actions. Battery, supply, valve-position and control faults should be investigated under site procedures. Maintenance reduces exposure to failure but cannot promise failures will never occur.
7. Specifying an FB Bombas assembly
To request an assembly, gather flow, head, suction, driver and control requirements. Identify pumps, valves, instruments, manifolds and components to integrate on the base. Also describe reservoir, piping, power and pump-room interfaces.
FB Bombas is a Brazilian manufacturer founded in 1944, with its factory in Cabreúva, São Paulo, and its FBE 2026 catalogue lists fire fighting as a product line of its own, alongside the FBE, FBEI, FBCN and FBOT series. Use the technical enquiry to confirm the proposed configuration, drawings, curves and assembly scope.
Lead time, warranty, support and commissioning should be clear in the proposal so supplies can be compared.
Send hydraulic calculations, installation location and supply requirements. Identify missing inputs so technical assessment starts from verifiable conditions.
