Skip to main content
FB BOMBAS

NFPA 20: What the Standard Requires from the Fire Pump System — Main, Diesel Standby and Jockey

NFPA 20 is the worldwide reference for stationary fire pump installation — and the technical basis cited in Brazilian Technical Instructions and specifications. Manufacturer guide: the three system pumps, the panel, the required curve, the complete skid and the mistakes that fail specification.

Selection
Published on April 10, 20267 min read·FB Bombas Engineering Team

TL;DR

  • An NFPA 20 fire system consists of three pumps: electric main, diesel standby and jockey for pressurization.

  • The main pump uses the FBCN series, a normalized centrifugal pump with 53 models, up to 2,200 m³/h and back-pull-out design.

  • FB Bombas supplies the complete system pre-assembled on a skid, with automatic panel, valves and the diesel standby pump.

  • FB Bombas delivers the system pre-assembled on a skid and commissions the electric, diesel and jockey start at acceptance, per NFPA 20 and NBR 16704.

Quick answer

An NFPA 20 fire protection system consists of three pumps: the main pump (electric), the standby pump (diesel engine for power-failure emergency) and the jockey pump (network pressurization to maintain constant pressure and avoid unnecessary main pump starts). FB Bombas uses the FBCN series as the base for fire pump systems, supplying the complete pre-assembled skid with automatic control panel, valves and accessories, compliant with NFPA 20, NBR 10897 (sprinklers), NBR 13714 (hydrants) and NBR 16704 (stationary fire pumps).

1. Applicable standards: NFPA 20 and ABNT family

Fire protection system design in Brazil follows two references: the international standard NFPA 20 (National Fire Protection Association) and Brazilian ABNT standards. Understanding the scope of each is the first step to correct specification.

  • NFPA 20 — International standard for stationary fire pump installation. Defines requirements for main pump, standby, jockey, controllers and testing
  • NBR 10897 — Fire protection by automatic sprinkler. Defines flow and pressure at nozzles
  • NBR 13714 — Hydrant and hose reel systems for fire fighting
  • NBR 16704 — Stationary pumps for fire protection. Brazilian standard specific to the pumps (the "Brazilian NFPA 20")

2. The three system pumps: main, standby and jockey

NFPA 20 requires redundancy. The complete system has three pumps with distinct functions:

PumpDriveFunctionWhen it operates
MainElectric motorProvides flow and pressure to the sprinkler and/or hydrant systemAuto-start on network pressure drop
Standby (diesel)Diesel engineTakes over during power failure or main pump failureAuto or manual start. Diesel tank autonomy per standard
JockeyElectric motor (smaller)Maintains constant network pressure. Compensates leaks and variationsOperates continuously at low flow. Prevents unnecessary main pump starts
Functions of the three pumps in an NFPA 20 fire system

3. Main pump — FBCN for fire systems

FB Bombas uses the FBCN series (normalized centrifugal) as the main pump in fire pump systems. The FBCN meets NFPA 20 and NBR 16704 requirements with the following characteristics:

  • Flow: sized per system demand (sprinklers + hydrants + reserve)
  • Pressure: per building height + friction losses + minimum pressure at the most remote nozzle
  • Back-pull-out construction: maintenance without disconnecting piping (essential for system availability)
  • Materials: cast iron (standard) or steel for saltwater or additive applications
  • Speed: up to 3,500 rpm per FBCN manual

4. Pre-assembled skid: what it includes

FB Bombas supplies the complete system pre-assembled on a metal skid, ready for on-site installation. The typical scope includes:

  • Main pump (electric motor) sized for the project
  • Standby pump (diesel engine) with fuel tank and starting battery
  • Jockey pump for continuous pressurization
  • Automatic control panel (pressure switch start, alarms, monitoring)
  • Gate, check, relief and test valves
  • Suction and discharge manifolds with flanges
  • Structural metal base with leveling feet

5. The curve the standard demands — and the tests that prove it

A fire pump is not an ordinary centrifugal pump painted red — NFPA 20 imposes a specific curve shape. The pump must deliver 150% of rated flow at no less than 65% of rated pressure, and shut-off pressure (zero flow) cannot exceed 140% of rated. This geometry guarantees two things at once: real capacity reserve when the fire opens more hydrants or sprinklers than the design assumed, and protection of the network against overpressure when demand drops.

Proof happens at two moments. At the FAT (factory acceptance test), the pump runs on the test bench with calibrated measurement at the three curve points — shut-off, 100% and 150% of rated flow. At field commissioning, the test is repeated on the real installation, with the definitive suction system and electric or diesel supply. Specifying without requiring both documented tests means giving up the only objective evidence that the system delivers what the hydraulic design calculated.

6. Specification mistakes that cost system approval

The most expensive problems surface at the Fire Department inspection or the insurer audit — when fixing means construction work. Four mistakes account for most rejections:

  • Specifying an ordinary centrifugal pump instead of one with an NFPA 20-compliant curve — it meets rated flow and pressure but fails the curve-shape requirement
  • Entrusting backup to a generator shared with other building loads — without NFPA 110 Level 1 qualification, the correct alternative is a dedicated diesel-driven pump
  • Omitting the jockey pump — the main pump starts on every small pressure drop, accumulating cycles that neither the standard nor the set's service life tolerates
  • Treating documentation as bureaucracy — without certified curve, data book and test records, approval stalls even with a physically correct system

7. Where it applies: building types and industries

Fire pump systems are required by law or insurers across various building categories and industrial facilities:

  • Shopping centers, hospitals and condominiums — sprinklers + hydrants per NBR 10897 and NBR 13714
  • Logistics warehouses and storage facilities — areas with high fire load
  • Refineries, power plants and fuel terminals — NFPA 20 requirement by risk class
  • Sugar-ethanol mills — combustible bagasse + flammable ethanol
  • Pulp and paper mills — fibrous materials and boilers

FB lines applied in this article

FBCN SeriesFire-Fighting

Related articles

Technical terms in this article

Full glossary

Ready to quote your centrifugal pump?

Direct quote on FBCN line (53 models ASME B73.1 — 43 standard + 10 large) from engineering in Cabreúva-SP. Reply after briefing analysis.

Request FBCN quote