Skip to main content

Manufacturer of Fire Pump Skid

A pre-assembled pumping package for the fire-protection network, designed to NFPA 20 or NBR 16704. The electric, diesel or combined configuration comes from the hydraulic design; FB does not supply UL/FM-listed packages.

Fire pumps on pallets in a workshop, from the FB Bombas collection
Fire pumps — photograph from the FB Bombas collection.
NFPA 20
Installation of fire pumps
NBR 16704
Brazilian stationary fire pump standard
CNC
Machining and assembly in Cabreúva-SP
1944
Brazilian manufacturer since
Fire pumps on pallets in a workshop, from the FB Bombas collection
Fire pumps — photograph from the FB Bombas collection.

What is a fire pump skid

A fire pump skid integrates pumping components on a common base to serve the protection network. The supply list may include pumps, drives, controllers, instruments, valves and interconnections. Flow, pressure, configuration, interfaces and documentation are defined by the design and proposal. Factory assembly does not eliminate installation checks, commissioning or field acceptance.

Configurations: electric, diesel or combined

Define drives and redundancy from the design and installation requirements

Electric Skid

A configuration with an electrically driven main pump. The proposal identifies the included jockey pump, controllers and accessories. Specify the power supply, starting conditions and project continuity requirements.

Best for: Projects that specify an electric drive and its power supply.

See configuration in detail

Diesel Skid

A configuration with a diesel-driven main pump. Specify the engine, starting system, fuel supply, exhaust, cooling and controller together. Testing and maintenance procedures depend on the installation and applicable requirements.

Best for: Projects that specify a diesel-driven pump.

See configuration in detail

Electric + Diesel Skid (Redundant)

A configuration combining electrically and diesel-driven pumps. The design defines each pump's role, control logic, controllers and interfaces. The presence of both drives alone does not establish compliance with all installation requirements.

Best for: Projects requiring different drive sources.

See configuration in detail

What composes the skid

Check the included equipment and supply boundaries in the proposal

Centrifugal main pump

FBCN normalized centrifugal pump, end-suction construction with back pull-out disassembly, sized for the total system demand (flow × pressure) per design. Automatic start via pressure switch on network pressure drop.

Jockey pump

The jockey pump maintains network pressure and avoids main-pump starts caused by small pressure losses. Flow, head and control settings must follow the design; it does not replace the main pump in meeting fire demand.

Dedicated control panels

Controllers operate the specified drives and provide the defined supervision and signaling functions. Confirm starting logic, alarms, interfaces and required documents for each configuration, including inspection and test procedures.

Pressure switches and instrumentation

Calibrated pressure switches continuously monitor network pressure, with two-level setting: jockey start pressure and main pump start pressure. Gauges and sensors complete the system readings.

Diesel auxiliaries

A diesel configuration requires the engine, fuel, batteries and chargers, exhaust and cooling to be defined for the equipment and design. Confirm capacity, supply and interfaces in the component list; do not assume one voltage or autonomy for every package.

Structural base, valves and piping

The baseplate organizes package assembly and interfaces. Materials, interconnections, supports, valves and lifting should be included in the approved scope. Piping loads and foundation conditions must be checked in the installation design.

Documents to define acceptance

Confirm the documentation required by the design, local authority and purchaser

Curve and duty point

Specify the performance points and records required for the selected pump. Check equipment identification and consistency between the design, proposal and documents.

ART and technical dossier

Confirm design and installation responsibilities, applicable professional responsibility records, and the manuals and drawings included in supply. Local acceptance depends on the process and requirements of the authority having jurisdiction.

Pre-assembled skid or field assembly?

Direct comparison for the design decision

Installation time

FB Bombas skid

Installation and commissioning timing is defined according to the configuration, site conditions and activities specified in the project.

Field assembly

The schedule should include field assembly, alignment, integration and testing according to the project.

Technical accountability

FB Bombas skid

Define responsibility for the pump, assembly, panels, documentation and site interfaces in the proposal.

Field assembly

Define responsibility boundaries between suppliers and the parties responsible for installation and integration.

Assembly quality

FB Bombas skid

Factory assembly organizes the package before transport. Alignment and installation conditions must be checked again on site.

Field assembly

The assembly plan should record alignment, support, integration and checks performed by the site team.

Standards governing the fire pump skid

NFPA 20 covers installation of stationary fire-protection pumps; NFPA 25 covers inspection, testing and maintenance of water-based protection systems. In Brazil, the design must identify applicable ABNT standards and Fire Department requirements. The proposal must record the requirements and documents included in supply.

Frequently Asked Questions

Technical answers from FB engineering

What is a fire pump skid?

It is a configuration that integrates fire-pumping components on a common base. The supply list defines included pumps, drives, controllers, instruments, valves and interconnections. Field installation, commissioning and acceptance must follow the design and applicable procedures.

What does a "certified" fire pump skid mean?

In practice, the word covers three different things. The first is the certified shop test curve, showing the pump's head-capacity and brake horsepower, which NFPA 20 requires the manufacturer to furnish to the purchaser (4.5.1). The second is the field acceptance test: once installed, the pump, driver and controller are tested as a complete unit (NFPA 20, 4.4.1, 4.4.2 and Section 14.2). The third is listing or certification of the package or of a component. Where the design adopts NFPA 20, the standard requires the fire pump to be listed for fire protection service (4.7.1) and the packaged assembly to be listed for fire pump service (4.31.1); listing or certification is proven only by the document issued by the body that granted it, stating the model and scope assessed. Citing NFPA 20 or NBR 16704 names the design standard, not a certification: request the documents the design requires and check that they correspond to the equipment offered.

Which components are included in the skid?

The configuration may combine a main pump, drive, jockey pump, controllers, instruments, valves and internal piping. Included components, interfaces and electrical requirements must appear in the approved supply list and drawing. Do not assume accessories or electrical configurations without confirmation in the proposal.

Electric, diesel or combined skid — which to choose?

Selection must follow the fire-protection design, available power supply and applicable redundancy requirements. Provide the required configuration and installation conditions to the technical team. The inspection, testing and maintenance plan must identify the procedures and intervals applicable to the installed system.

What is the difference between the skid and a conventional pump house?

Compare field assembly and a pre-assembled skid by the supply list, installation activities and responsibilities. The pre-assembled package integrates the pump, drive, panel and interconnections at the factory. The schedule and civil works depend on the project and site conditions.

How long does the fire pump skid take to be ready?

Lead time depends on the configuration, components and approved scope. Confirm the design, manufacturing, documentation and shipment milestones in the proposal.

Does the skid meet my state Fire Department Technical Instruction?

Provide the state, occupancy, hydraulic design and requirements of the responsible authority. The team must check the offered scope against those documents before contracting. Installation approval is a separate process of the authority having jurisdiction and is not automatic upon purchasing the skid.

How to request a fire pump skid quote?

Send design flow and pressure, network type, required drives, suction conditions, power supply and available space. Attach the hydraulic design and documentation and test requirements. The technical proposal must define the package, interfaces, supply boundaries and responsibilities.

Ready to quote your fire pump skid?

Send design flow and pressure, network type and the applicable Technical Instruction. The proposal should define the package, interfaces and supply documents; installation approval rests with the competent authority.