FBFS online catalogue
Configurations and technical references for the line.
View catalogueElectric System — FB Bombas Fire Fighting System — NFPA 20 · ABNT NBR 16704 — Manufacturer since 1944

Electric main pump, jockey pump and automatic controls.

Review the drive and the points to define in the project.

Reference photograph of the drive assembly. Accessories and the supplied layout are defined by the project.
Fire pump system with an electric motor-driven main centrifugal pump, a jockey pump for pressure maintenance and automatic controls. Pump, motor, controller and interfaces are defined from the hydraulic demand and power supply specified by the project.
For projects specifying an electric main pump. Available power and its requirements need to be assessed with the fire protection design.
Final selection depends on the fire protection project and installation requirements. A configuration alone does not determine flow, pressure or installation approval.
Series rating Fire Fighting Systems: 4.9/5 · 52 customer ratings
Consolidated figures supplied by FB Bombas from its customer ratings spreadsheet. The score and count refer to the series; they are not independent counts for each model or configuration.
What makes up the Electric System and what each item must meet. Each card shows its source: the FBCN manual, São Paulo IT 22 or NFPA 20, where the contract adopts it.
FBCN series centrifugal pump, selected from its curve for the project flow and pressure. Per the series manual, the spiral casing is cast in one piece, the impeller is a single-suction radial design, construction is back-pull-out and sealing is by packing or mechanical seal.
Source: FBCN manual MTEC-03/00, p.1 and p.7Drives the main pump and is checked against its nameplate: manufacturer, type, model, serial number, power in CV, speed, voltage, current and frequency (IT 22, C.2.16). Where the contract adopts NFPA 20, the motor complies with NEMA MG-1, is marked as NEMA Design B when three-phase and is specifically listed for fire pump service (9.5.1.1).
Source: IT 22 SP · NFPA 20, ch. 9In São Paulo, IT 22 requires a supply independent of general consumption and the switch marked “ALIMENTAÇÃO DA BOMBA DE INCÊNDIO – NÃO DESLIGUE” (fire pump supply – do not switch off) (C.2.7 and C.2.11). Where the contract adopts NFPA 20,an alternate source is required when the normal source is not reliable or when the power is for a high-rise building, and it is not required when a backup diesel engine, steam turbine or electric pump with an independent source is installed (9.3.1 and 9.3.2).
Source: IT 22 SP · NFPA 20, 9.3Keeps the network pressurised within preset limits while there is no flow and makes up small losses, without replacing the main pump. In São Paulo, networks with more than six outlets use a jockey of no more than 20 L/min, unless there is an elevated tank, and its maximum pressure is the main pump shutoff (IT 22, C.1.15 and C.1.15.1). Where the contract adopts NFPA 20,the jockey pump need not be listed but must be approved, and its controller is listed, though not for fire pump service (4.27.2 and 4.27.8).
Source: IT 22 SP · NFPA 20, 4.27Selected by motor power in CV, with magnetic starting and acceleration of no more than 10 seconds, it is installed as close as possible to the motor, protected against splashes and dust. It is supplied with dimensional drawings, layout, wiring diagram, terminal strip, internal diagram and bill of materials (IT 22, C.2.17 and C.2.18).
Source: IT 22 SP, C.2.17–C.2.18On the automation manifold, pressure switches start and stop the jockey pump and only start the main pump, wired to the controllers and starters of each pump (IT 22, C.1.15.2). Where the contract adopts NFPA 20,each controller has its own sensing line, between the check valve and the discharge isolation valve of its pump, in brass, rigid copper type K, L or M or series 300 stainless steel, with 1/2″ (15 mm) fittings (4.32.1 to 4.32.3).
Source: IT 22 SP · NFPA 20, 4.32A pressure gauge on the discharge and, with suction lift, a compound gauge on the suction (IT 22, C.1.17); the FBCN manual provides 1/4″ NPT tappings for both (p.12). Where the contract adopts NFPA 20, each pump has a circulation relief valve ahead of the check valve, 3/4″ up to 2,500 gpm and 1″ from 3,000 to 5,000 gpm, not required on a diesel pump whose engine cooling water comes from its own discharge (4.13 and 4.13.1.2).
Source: IT 22 SP · FBCN manual, p.12 · NFPA 20, 4.13The FBCN pump set includes the driver, coupling, coupling guard and baseplate (manual MTEC-03/00, p.8). The main pump is coupled directly by a flexible sleeve coupling, without belts or chains (IT 22, C.1.5), and alignment follows the coupling and pump manufacturers and, where the contract adopts NFPA 20, ANSI/HI 1.4 (6.5.2). Check the alignment on site, after transport and anchoring.
Source: FBCN manual, p.8 · IT 22 SP, C.1.5 · NFPA 20, 6.5IT 22 applies in São Paulo; other Brazilian states have their own rules. Engine and controller manufacturers, final composition and supply scope are defined in the technical proposal.
| Component | Electric | Diesel | Electric + diesel |
|---|---|---|---|
| FBCN main pump | Included | Included | 2 pumps |
| Electric motor | Included | Not applicable | Included |
| Power supply | Included | Not applicable | Included |
| Diesel engine | Not applicable | Included | Included |
| Jockey pump | Included | Included | Included |
| Electric pump controller | Included | Not applicable | Included |
| Diesel engine controller | Not applicable | Included | Included |
| Pressure switches and sensing line | Included | Included | Included |
| Gauges and valves | Included | Included | Included |
| Starting batteries | Not applicable | Included | Included |
| Fuel tank | Not applicable | Included | Included |
| Cooling and air | Not applicable | Included | Included |
| Exhaust | Not applicable | Included | Included |
| Baseplate and coupling | Included | Included | Included |
How the jockey and main pumps come into operation: the settings proposed in the NFPA 20 annex and the São Paulo IT 22 sequence.
Annex example: 1,000 gpm, 100 psi pump with a 115 psi churn pressure and a city supply with 50 psi minimum and 60 psi maximum static pressure (1 psi = 0.0689 bar).
Final settings come from the pressures read on the test gauges. In São Paulo, IT 22 recommends a differential of approximately 10 m of water (100 kPa) between sequential starts (C.1.15.1).
The manifold pressure switches start and stop the jockey pump automatically (C.1.15.2).
Opening any hydrant point starts automatic operation, and the pressure switch only starts the main pump (C.1.8 and C.1.15.2).
The pump reaches full speed in about 30 seconds; with an electric motor, acceleration takes up to 10 seconds (C.1.9 and C.2.18).
Manual only, at its own panel in the pump house, with at least one manual start point in a safe, accessible location (C.1.6 and C.1.7).
Construction data for the centrifugal pump fitted to the FBFS, from the series manual, and the curve limits the project checks when it adopts NFPA 20.

Series limits, which do not apply at the same time: the fire duty point comes from the curve selected for the project. In São Paulo, IT 22 does not recommend pumps above 100 m of water column (1 MPa) (C.1.13 and C.1.14).
Where the contract adopts NFPA 20, the centrifugal pump delivers at least 65% of rated pressure at 150% of rated flow, and shutoff is no more than 140% of rated pressure (6.2.1 and 6.2.2). For the field acceptance test, the annex lists shutoff, rated flow and 150% of rated flow as the important points (A.14.2.6.3). The chart shows limits, not the curve of a model.
Consult the online catalogue and state the project standards. Supplied assembly documents should match the agreed configuration.
Configurations and technical references for the line.
View catalogueCentrifugal pump documentation. Also consult the motor and controller manuals for the supplied assembly.
View manualThe list for each supply is agreed in the proposal. Purchasing the assembly does not automatically approve the installation.
NFPA 20 and ABNT NBR 16704 address pumping assemblies. Sprinklers and hydrants have their own references, depending on the specified system. A design standard is not a product certificate.
A well-prepared enquiry helps assess the assembly, installation conditions and documentation required by your project.
Provide flow, pressure, suction conditions, building type, planned drive and required project standards.
Engineering reviews the pump, driver, controls and interfaces. Layout, power supply and installation conditions inform the proposal.
Agree on the assembly drawing, performance curve, test reports and manuals within the supply scope.
The package is assembled on its base according to the scope. The pump undergoes a bench performance test per ANSI/HI 14.6 and a hydrostatic test; a certified curve and FAT are supplied when the order requires them.
Answers to help compare configurations and prepare your technical enquiry.
Fire pump system with an electric motor-driven main centrifugal pump, a jockey pump for pressure maintenance and automatic controls. Pump, motor, controller and interfaces are defined from the hydraulic demand and power supply specified by the project.
Provide the configuration of interest, required flow and pressure, suction conditions, available drive and installation location. Include the specification, layout and required standards if available. You can start the enquiry with the information you have and complete it with the team.
The jockey pump maintains network pressure and compensates for small losses. It avoids unnecessary main pump starts but does not replace the pump responsible for fire fighting demand. Selection needs to account for installation conditions.
Use the fire protection project demand, considering the served system, pipe network, suction conditions and pump duty point. An electric or diesel configuration does not have one fixed flow or pressure. Send these requirements to engineering for assembly selection.
No. They are standards for fire pumping assemblies. NFPA 20 addresses stationary pump selection and installation; ABNT NBR 16704 addresses pump assemblies for fire protection. The project should specify applicable requirements. Supply test reports and installation approval are separate documents.
Agree on the assembly drawing, performance curve, test reports and pump, driver and controller manuals in the proposal; FB defines deliverables per project, such as the data sheet, Q×H curve, dimensional drawing, FAT plan and bench test certificate. On the curve, check the envelope: at least 65% of rated pressure at 150% of rated flow and a shutoff of no more than 140% of rated pressure (Hydraulic Institute). For the field acceptance test, the NFPA 20 annex lists shutoff, rated flow and 150% of rated flow as the important test points, with speed and suction and discharge pressures recorded at each point (A.14.2.6.3). State the project, responsible engineer and local authority requirements before supply. Purchasing the assembly does not automatically approve the installation.
Send the current assembly identification and documents, required duty point, connections, available space and power supply conditions. Engineering assesses the new supply against the project and existing interfaces.
Send the information you already have. Your selected configuration stays with the enquiry so our team can follow up in context.
Review the other configurations before specifying the system.

Diesel main pump, jockey pump and dedicated controller.
A diesel engine drives the main pump without relying on an electric motor. Fuel, starting, ventilation and exhaust are part of the assembly specification.


Electric pump, diesel pump and jockey pump in one project.
Combines electric and diesel drives where this arrangement is specified. Each pump’s duty, controls and supply are defined by the project.
Photographs of FB Bombas equipment. The final scope is defined in the technical proposal.
Explore applications, installation or supply while keeping your fire protection project in context.