1. Boiler feed water pump: feed, condensate and high temperature
The boiler feed water pump supplies the steam generator from the deaerator or the feed and condensate tank. Flow starts from the boiler water and steam balance: steam output plus blowdown. NPSH available is the critical point, because the water arrives close to saturation: with saturated liquid in the vessel, vessel pressure and vapor pressure cancel out in NPSHa = (Pabs − Pv)/(ρ·g) + z − hf, leaving only the liquid height above the pump minus suction losses.
That is why the pump is installed below the vessel, with enough height to cover the required NPSH, the margin and the losses, and with a short, unrestricted suction.
Discharge pressure is the suction pressure plus what the pump generates, Δp = ρ·g·H, and it must exceed the boiler pressure plus the elevation difference and the losses up to it. With water at 100 °C (958 kg/m³, NIST), 135 m — the FBCN series maximum head — equals about 12.7 bar (1,270 kPa), and 300 m — the FBME maximum — about 28 bar (2,820 kPa).
These are series maxima, not simultaneous with maximum flow: the actual duty comes from the model curve. In both series suction goes up to 10 bar; FBCN discharge follows the pressure × temperature curves of Figures 1 to 4 of MTEC-03/00, and FBME discharge goes up to 30 bar at zero flow (MTEC-08/01).
For comparison, NR-13, the Brazilian regulation on boilers and pressure vessels, classifies as category A a boiler with an operating pressure equal to or above 1,960 kPa (19.98 kgf/cm²; item 13.4.1.1).
NR-13 also requires every boiler to have an automatic water level control system with an interlock that prevents overheating due to insufficient feed (item 13.4.1.2, subitem e) and, in boilers burning non-atomized solid fuel or with suspension firing, an injector or water feed system independent of the main one (subitem c).
These items belong to the boiler and its design; when ordering the pump, state whether it will be the main or the independent feed and what standby the design provides.
At high temperature, sealing has its own limit, which is not the general series rating:
- FBCN without cooling chamber: packing from −50 to 105 °C; mechanical seal as recommended by the seal manufacturer (Table 1 of MTEC-03/00)
- FBCN with cooling chamber: packing up to 350 °C in sizes 25-150 to 150-315 (100-500 included), with cooling-water flow by temperature and up to 7 bar in the cooling liquid (Table 1); with water, vapor pressure and the 10 bar suction limit govern first
- FBCN seal chamber arrangements (section 10 of MTEC-03/00): standard ST, lubricated by the pumped fluid, up to 160 °C; S1, S2 and S3, with liquid from an external source, up to 105 °C and without a cooling chamber; S4, with graphite packing, for thermal oil above 260 °C
- FBME: packing from −10 to 105 °C without cooling and from 105 to 140 °C with cooling (Table 1); in the S4 arrangement (above 105 °C and below 140 °C, with suction pressure above 1 bar), cooling water enters at no more than 40 °C and leaves at no more than 60 °C, at up to 6 bar (Figure 3); single mechanical seal per the seal manufacturer: without cooling, up to about 105 °C (Figure 3), with a 140 °C maximum in Table 1 (MTEC-08/01)
2. Technical challenges of pumping hot and high-temperature water
Vapor pressure, thermal expansion and sealing limits need assessment in any installation. With hot water, and even more at high temperature above 100 °C, rising vapor pressure reduces suction margin, and temperature differences make clearance and alignment checks under the assembly procedure relevant. A general series temperature limit never replaces pressure, liquid-phase and construction checks.
The table uses vapor pressure and density of saturated water from the NIST Chemistry WebBook; the column in meters was converted with the water density at the same temperature, which is how NPSH must be calculated. In the FBCN manual, pressure is also limited by sealing and flange.
With ANSI B16.1 flanges, the cast iron ones in Table 1, Table 3 allows with packing 12 bar from −28 to 65 °C, 11 bar at 93 °C and 10 bar at 105 °C in class 125 lb, and 16 bar from −28 to 105 °C in class 250 lb; with a mechanical seal, 10 bar at 90 °C in both classes.
| Temperature | Vapor pressure (bar abs) | In meters of the liquid itself | Consequence for suction |
|---|---|---|---|
| 20 °C | 0.023 | 0.24 | Include in the calculation even though lower than at the following temperatures |
| 60 °C | 0.199 | 2.07 | Reduces NPSH available by about 2 m |
| 90 °C | 0.702 | 7.41 | Reduces NPSH available by about 7.4 m |
| 100 °C | 1.014 | 10.79 | In an open vessel at sea level, water boils: NPSH available comes only from the liquid column minus losses |
| 120 °C | 1.987 | 21.48 | Exists as a liquid only in a system pressurized above this pressure |
| 140 °C | 3.615 | 39.81 | FBME maximum temperature (MTEC-08/01); liquid only with the system pressurized above this pressure |
| 160 °C | 6.182 | 69.47 | Liquid only with the system pressurized above this pressure; also the limit of the FBCN standard ST arrangement and of the cast iron casing (section 10 and Figure 1 of MTEC-03/00) |
| 180 °C | 10.03 | 115.3 | Closed system pressurized above 10 bar abs |
Engineering note
FBCN suction pressure is limited to 10 bar in MTEC-03/00. The general 260 °C rating therefore does not establish water pumping at 260 °C, where saturation pressure is 46.9 bar absolute. At 180 °C, water already saturates at 10.03 bar absolute (NIST), close to that limit before any NPSH margin. At the design temperature, also check casing and flanges (Figures 1–4), packing and cooling chamber or mechanical-seal limits. All must be compatible simultaneously.
3. Typical hot water pump applications
Hot water pumps serve two groups: industrial (boilers, thermal processes, heat recovery, cooling towers) and building (HVAC, sanitary hot water, collective solar heating), in office buildings, hospitals, hotels, residential buildings, shopping centers and data centers. Flow, pressure, temperature and duty come from the design of each installation; what changes from one application to another is which of the three limits usually governs.
- Boiler feed and recirculation: treated water close to saturation, and feed pressure must exceed boiler pressure — above the FBCN envelope (135 m), assess the FBME, with up to 300 m and 140 °C in the general data of MTEC-08/01; the calculation is in section 1
- Cooling towers: open circuit with make-up water and chemical treatment; solids, biocides and chlorides define material and sealing
- HVAC (chilled and hot water): closed circuit between chiller or boiler and fan-coils or AHUs, where head is almost only friction loss and flow comes from the thermal load
- Condensate return: water close to saturation in the condensate tank — NPSH available is the critical point (section 1)
- Sanitary hot water in hotels, hospitals and residential buildings: recirculation to keep network temperature when there is no draw-off (WHO guidance: ideally above 50 °C in distribution)
- Collective solar heating (ABNT NBR 15569): circulation between collectors and storage, controlled by temperature differential
4. Building HVAC: chiller, fan-coil and flow control
In building HVAC, the pump circulates chilled or hot water between the chiller or boiler and the fan-coils and air handling units (AHUs). Circuit volumetric flow follows the heat balance: Q = P / (ρ × cp × ΔT), in m³/s when P is in W, ρ in kg/m³ and cp in J/(kg·K). Hypothetical example: 1,000 kW, water with ρ = 1,000 kg/m³ and cp = 4,180 J/(kg·K), and a 5 K ΔT give 0.0478 m³/s, about 172 m³/h.
Glycol mixtures or another temperature require the corresponding properties.
In a completely filled closed loop, elevation does not add to circulation head: the pump overcomes circuit losses. Static pressure still matters for casing, flanges, sealing and suction. With variable demand, compare the system curve and control strategy; affinity laws do not guarantee fixed savings or replace efficiency and minimum-flow checks for the pump and equipment.
ABNT NBR 16401-1 (Air conditioning installations — Central and unitary systems) sets basic parameters and design requirements for central and unitary air conditioning systems; pump redundancy (1+1 or N+1) is a design decision, according to how critical the space is and the standards that apply to it. To select the FBCN, FB needs: flow and head at the design point, operating temperature, system static pressure and control strategy.
In tall buildings, add the circuit fill pressure to the pressure generated by the pump and check the 10 bar suction limit and the discharge pressure × temperature of Figures 1 to 4.
5. Sanitary hot water and solar heating: recirculation and forced circulation
For sanitary hot water (domestic hot water, DHW), ABNT NBR 5626 (Cold and hot water building systems — Project, execution, operation and maintenance) specifies requirements for design, installation, operation and maintenance. For recirculating systems, WHO indicates water leaving the heater at no less than 60 °C and returning at no less than 50 °C, outside the 25 to 45 °C range in which Legionella survives and multiplies; safe outlet temperature, against scalding, is also part of the design.
The recirculation pump is sized by the network heat loss, not by the draw-off flow: Q = Φ / (ρ · cp · ΔT), where Φ is the piping loss (W/m × length) and ΔT the allowed drop between heater outlet and return, up to 10 K with a 60 °C outlet.
Example with margin, ΔT of 5 K: 200 m of network losing 10 W/m (2 kW) requires about 0.1 L/s (0.34 m³/h), and head is the loop friction loss at that flow. Compare with the operating range of the smallest FBCN model (minimum flow of 0.1 to 0.15 × best-efficiency flow); very small flows call for compact circulators, outside the scope of the reviewed FB catalogues.
For direct-circuit solar water heating, ABNT NBR 15569 (Direct solar water heating system — Design and installation requirements) establishes the design and installation requirements. In a thermosiphon, circulation is natural and depends on the storage position relative to the collectors; in forced circulation, the pump is controlled by a differential temperature controller between collectors and storage, flow per collector area comes from the collector manufacturer and head is the circuit friction loss.
Small systems use compact circulators; the FBCN comes in for collective and industrial installations when flow and head fall on the curve of a series model, checking the maximum circuit temperature and the sealing limit.
Warning
The recirculation pump alone does not guarantee Legionella control: heater temperature, insulation, removal of dead legs and the building water management plan are part of the same system. FB sizes the pump for the heat loss and friction loss provided by the design.
6. Materials and chemical compatibility with treated water
Hot water is rarely pure water. In closed HVAC and boiler circuits, water receives corrosion inhibitors, biocides and anti-scalants defined by the treatment supplier; in sanitary hot water there is residual disinfectant. Compatibility of casing, impeller and sealing with these products is confirmed with the treatment supplier and the seal manufacturer. The casing options documented for the FBCN are cast iron, A216 WCB carbon steel and A743 CF8M stainless (MTEC-03/00).
| Application | Casing (FBCN options) | Sealing | What to confirm |
|---|---|---|---|
| Boiler and condensate | Cast iron up to 160 °C (Figure 1); WCB or CF8M up to 260 °C (Figure 2), by pressure × temperature | Packing with cooling chamber above 105 °C, or seal per its manufacturer | NPSH close to saturation; discharge pressure |
| Treated closed-circuit HVAC | Cast iron, WCB or CF8M | Mechanical seal or packing, by temperature | Chemical treatment; static pressure at suction |
| Sanitary hot water (potable) | CF8M when the specification calls for stainless; others per the project sanitary specification | Mechanical seal with materials accepted by the design | Sanitary requirements for materials in contact with drinking water |
| Collective solar heating | Cast iron or CF8M | Mechanical seal | Maximum circuit temperature; water or antifreeze mix in an indirect circuit |
| Cooling tower | Cast iron, WCB or CF8M | S2/S3 packing or mechanical seal | Solids, biocides and chlorides of the make-up water |
7. Maintenance and real problems: scale, biofouling and Legionella
Scaling and biofilm growth depend on chemistry, temperature and operation; they can also occur in cold water. According to WHO, scale and corrosion are among the risk factors for biofilm: they increase the available surface area, form microniches protected from circulating disinfectants and raise the concentration of nutrients such as iron. Monitor treatment and water quality to interpret performance loss or sealing failures. Pump routines should consider the points below and the specific instructions for the installed assembly.
- Bearing oil level and condition: the FBCN is oil-lubricated, with dipstick or optional automatic oiler (Table 1 of MTEC-03/00)
- Packing: it needs some leakage to lubricate itself; with external liquid, the manual gives about 1 L/min for sealing and 3 to 5 L/min for flushing (Table 1)
- Cooling chamber, when present: check the water flow given for the pumping temperature — for example, 1.2 to 3.8 L/min at 140 °C and 3.0 to 7.2 L/min at 250 °C, depending on the bracket — and the 7 bar limit for the cooling liquid (Table 1)
- Mechanical seal: temperature, pressure and fluid within the seal manufacturer limits; leakage above what it allows calls for inspection
- Vibration and bearing temperature: follow the trend against the baseline of the new pump
- Water chemistry: pH, hardness, conductivity and treatment residual, at the frequency defined by the treatment supplier
- Sanitary hot water: temperature at the return and at the farthest point according to the building water management plan
Key point
Before ordering, send application engineering: operating and maximum temperature, flow, head, system static pressure, water analysis, preferred sealing type and control strategy. With these data, FB indicates model, casing, sealing and, if needed, cooling chamber, and records the scope in the proposal.
8. How to select the hot water pump: 8 steps
Hot water pump selection follows 8 steps. Missing data in any of them can change the model, casing or sealing indicated.
- Define flow from Q = P / (ρ × cp × ΔT) with consistent units; for boilers, include the process water/steam balance
- Calculate total head: static + distributed losses + local losses + residual pressure; in a closed circuit, practically only the losses
- Determine operating and maximum temperature: it defines the sealing arrangement (Table 1) and the pressure × temperature check of casing and flanges (Figures 1 to 4)
- Calculate NPSHa = (Pabs − Pv)/(ρ × g) + z − hf: pressures in Pa, z positive when level is above the pump, losses in metres; check the design margin above NPSHr
- Analyze water chemistry (pH, hardness, conductivity, disinfectant residual, inhibitors) to choose casing and sealing
- Check suction pressure: system static and fill pressure within the 10 bar FBCN limit (Table 1)
- Define control strategy and redundancy: fixed or variable flow with a drive; 1+1 or N+1 according to criticality
- Select the FBCN model with the operating point close to BEP and within 0.1–0.15 × to 1.1 × best-efficiency flow (Table 1); above 135 m, assess the FBME (up to 300 m and 140 °C)



